Frequently Asked Questions

Yes, across virtually all jurisdictions. Electrical safety regulations and utility O&M standards globally require insulating protective equipment at energized panels. IEC 61111 Class 2 is the referenced standard for international markets; IS 15652 Class B applies under Indian regulations; ASTM D178 Class 2 applies in the Americas.

They are not the same product. A mat "tested to 11kV" has an 11kV withstand test voltage, under IEC 61111, this corresponds to Class 0 or Class 1 range, with a maximum use voltage of 1.0 kV to 7.5 kV. These are not compliant for use in an 11kV system. A mat "for use at 11kV" must have a maximum use voltage that covers 11kV, which requires IEC 61111 Class 2 (17.0 kV max use) or IS 15652 Class B (11.0 kV working).

11kV rubber mat thickness requirements differ by standard: IS 15652 Class B is 2.5 mm minimum; IEC 61111 Class 2 is 3.0 mm recommended (maximum 8.0 mm); ASTM D178 Class 2 is 6.4 mm recommended. These figures are not safety-interchangeable, each is part of the standard's tested design basis. Verify actual thickness with a calibrated micrometer at delivery.

Check three items: (1) the type test certificate references IS 15652:2006 and Class B specifically; (2) the product label on the roll states working voltage of 11kV and a traceable product code; (3) thickness measurement confirms minimum 2.5 mm. All three must be confirmed before accepting the consignment.

Yes. A higher-class mat placed in a lower-voltage zone exceeds the protection requirement and is compliant. A Class 2 mat in a 3.3kV zone is technically acceptable. The reverse is never acceptable, a Class A or Class 1 mat used in an 11kV zone provides no certified protection at the operating voltage regardless of how it is described in a supplier's marketing material.